cooling Archives - Microway https://www.microway.com/tag/cooling/ We Speak HPC & AI Tue, 28 May 2024 04:24:29 +0000 en-US hourly 1 https://wordpress.org/?v=6.7.1 Power and Cooling (Multiple-Computer Installations) https://www.microway.com/knowledge-center-articles/power-and-cooling-multiple-computer-installations/ https://www.microway.com/knowledge-center-articles/power-and-cooling-multiple-computer-installations/#respond Tue, 30 Jul 2013 21:51:12 +0000 http://https://www.microway.com/?post_type=incsub_wiki&p=2663 This article applies to groups of computers which consume 1,000+ Watts of electricity. Review your quote or contact us to determine how much your systems will require (the power and cooling numbers are typically listed at the end of the quote – below the total cost of the system). Acoustic Considerations – Fan Noise Microway’s […]

The post Power and Cooling (Multiple-Computer Installations) appeared first on Microway.

]]>
This article applies to groups of computers which consume 1,000+ Watts of electricity. Review your quote or contact us to determine how much your systems will require (the power and cooling numbers are typically listed at the end of the quote – below the total cost of the system).

Acoustic Considerations – Fan Noise

Microway’s server systems provide intelligent cooling fans which ramp up and down with system load. However, most systems are very high-density with more than 1,000 Watts consumed per rack unit. Cooling such systems requires high-speed fans which generate significant noise. Most cluster systems will generate 60 dB to 80 dB. This noise level may be subject to safety regulations (e.g., OSHA) and will be audible from other offices in the building. It is recommended that your cluster be placed in a location designed for servers.

If noise is a concern, many of Microway’s workstations – most notably the WhisperStation – are designed to be very quiet and comfortable for an office environment. Quiet HPC Clusters built from Microway WhisperStations are available. If you have any concerns, discuss these matters with your salesperson. In general, if it’s not a WhisperStation you should consider whether the system is appropriate for a lab or office environment.

Power

Microway servers feature auto-switching power supplies which accept both 120V and 208V power, so there are a variety of options when powering multiple computers. The most common electrical circuits are pictured below. Your salesperson can provide a customized recommendation including the rackmount cabinet, power distribution units and optional UPS backup power.

In general, 208V is recommended over 120V. Using 208V allows more systems to run on a single circuit, and each system runs several percent more efficiently.
Diagram of common high power electrical receptacles

120V 20A NEMA 5-20 and L5-20 Electrical Outlets

After a 20% de-rating for safety, these circuits supply up to 1,920 Watts of power.

120V 30A NEMA L5-30 Electrical Outlets

After a 20% de-rating for safety, these circuits supply up to 2,880 Watts of power.

208V 20A NEMA L6-20 Electrical Outlets

After a 20% de-rating for safety, these circuits supply up to 3,328 Watts of power.

208V 30A NEMA L6-30 Electrical Outlets

After a 20% de-rating for safety, these circuits supply up to 4,992 Watts of power.

3-Phase 208V NEMA L21-20 Electrical Outlets

After safety de-rating, these circuits supply up to 5,700 Watts of power.

3-Phase 208V CS 8365 Electrical Outlets

After safety de-rating, these circuits supply up to 14,400 Watts of power. Depending upon which PDU is selected, the actual load on each PDU may need to be less – 10kW, 12.6kW or 14.4kW.

Before assuming a particular circuit layout will be sufficient for your new equipment, review:

  • Is other equipment already connected to the electrical circuit? It is common for multiple outlets to connect to the same circuit, so don’t assume that an empty outlet means power is available. You will need to perform an inventory of the power required by your existing equipment.
  • Particularly for smaller circuits: will you be able to evenly split your servers across multiple circuits? Three 1,000W systems will not successfully connect to two 1,500W circuits. Determine how much electricians will charge for installation of multiple circuits, because it is likely that a single large circuit will be a better choice.

Cooling

Groups of computers typically require special cooling arrangements – your building air-conditioning is designed for offices and will not be able to keep up with the load of compute servers. Note that some facilities reduce or shut down air-conditioning during holidays and weekends. Systems will overheat if they are run in a closed room without sufficient cooling.

A server room or datacenter is the best location for your systems. Microway servers and clusters are designed for installation in industry-standard rackmount cabinets, so you should have no concern when using your own cabinets. We can also provide cabinets with network and power cables pre-wired.

Many facilities specify a maximum power load per rackmount cabinet. You may be restricted to only 7kW or 10kW per cabinet, which would result in racks which are only half-filled. To be certain, present the cooling requirements (provided by your salesperson) to your facilities manager. Your facilities personnel will have details on the cooling load limitations of the datacenter/server room.

The post Power and Cooling (Multiple-Computer Installations) appeared first on Microway.

]]>
https://www.microway.com/knowledge-center-articles/power-and-cooling-multiple-computer-installations/feed/ 0
Power and Cooling (Single-Computer Installations) https://www.microway.com/knowledge-center-articles/power-and-cooling-single-computer-installations/ https://www.microway.com/knowledge-center-articles/power-and-cooling-single-computer-installations/#respond Wed, 17 Jul 2013 04:08:15 +0000 http://https://www.microway.com/?post_type=incsub_wiki&p=1652 This article applies to computers which consume less than 1920 Watts of electricity. Review your quote or contact us to determine how much your system will require (the power and cooling numbers are typically listed at the end of the quote – below the total cost of the system). Acoustic Considerations – Fan Noise Most […]

The post Power and Cooling (Single-Computer Installations) appeared first on Microway.

]]>
This article applies to computers which consume less than 1920 Watts of electricity. Review your quote or contact us to determine how much your system will require (the power and cooling numbers are typically listed at the end of the quote – below the total cost of the system).

Acoustic Considerations – Fan Noise

Most single computers can be powered and cooled within an office environment. However, some systems contain high-speed fans which generate loud noise. In some cases, an office worker may decide this is acceptable. In others, the noise may be subject to safety regulations (e.g., OSHA) and will be audible from other offices in the building.

Many of Microway’s workstations – most notably the WhisperStation – are designed to be very quiet and comfortable for an office environment. Other systems contain so many high-power components that they simply cannot be quietly cooled.

In contrast with other vendors, Microway does not re-brand servers as workstations. We will provide an honest assessment of system noise. If you have any concerns, discuss these matters with your salesperson. In general, if it’s not a WhisperStation you should consider whether the system is appropriate for an office environment.

Power

Most single Microway computers can be powered from a standard wall outlet. For groups of computers, there are better options than those listed below – see Power and Cooling for Multiple Computers.

Home / Small Office Electrical Outlets

Picture of NEMA 5-15 Electrical Outlet Domestic AC USAThese power outlets provide 15 Amps at 120V and are designated NEMA 5-15. After a 20% de-rating for safety, the NEMA 5-15 can supply up to 1440 Watts of power.

There are several cases when 15A 120V outlets are not sufficient:

  • Other equipment is already connected to the electrical circuit. It is common for multiple outlets to connect to the same circuit, so don’t assume that an empty outlet means power is available. You will need to perform an inventory of the power required by your existing equipment.
  • You would like to provide a backup power solution (UPS) and the system consumes more than 1000 Watts.
  • Servers with more than four GPU accelerators or coprocessors will consume more than 1440 Watts.
  • Your system is a Twin or Blade server which actually contains multiple computers. These systems almost always consume more than 1440 Watts.

Commercial Electrical Outlets

Picture of NEMA 5-20 Electrical Outlet Domestic AC USAThese power outlets provide 20 Amps at 120V and are designated NEMA 5-20. After a 20% de-rating for safety, the NEMA 5-20 can supply up to 1920 Watts of power.

This type of outlet is common in office buildings, medical centers and universities, but is not universal. Double-check to be certain your area actually has this type of power circuit. Also verify that it is not designated for special purposes, such as emergency power.

Although this outlet should be sufficient for almost all systems, consider:

  • Other equipment may already be connected to the electrical circuit. It is common for multiple outlets to connect to the same circuit, so don’t assume that an empty outlet means power is available. You will need to perform an inventory of the power required by your existing equipment.
  • Servers with more than four GPU accelerators or coprocessors may consume more than 1920 Watts.
  • If this is a Blade chassis with multiple computers, it will consume more than 1920 Watts.

Cooling

Systems in this category can typically be run without special cooling arrangements – the building air-conditioning will be able to keep up with the load.

Note that some facilities reduce or shut down air-conditioning during holidays and weekends. Many systems will overheat if they are run in a closed room without sufficient cooling. You may need to make special arrangements.

To be certain, present the cooling requirements (provided by your salesperson) to your facilities manager. Your facilities personnel should be able to determine if issues will occur.

The post Power and Cooling (Single-Computer Installations) appeared first on Microway.

]]>